E3M220 MS5 Adapter
111
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
27 E3M220 MS5 Adapter
27.1 Overview
NOTE The module E3M220 is not
CE-conform!
z Connection of existing MS5 detectors (220 VDC) to the CS1140 control unit
z Converts the signal on the MS5 detection line into a conventional detector signal
(collective 20 V)
z Designed for 2 detection lines with bi-directional signal conversion
z Only use in combination with the E3M080 line module
z Requires a separate supply 24 V
z Card format (100 mm x 200 mm)
z Number of MS5 detectors per detection line: FES5, DES5, MES5: unlimited
FES7.5: max. 25
RES5, SES5: max. 5
27.2 Key data
Operating status of the MS5 detection line Conversion Operating status of the collective line
Alarm AI flashes –> Alarm on corresponding line
Short circuit < 40 V Short circuit on corresponding line
Open line > 232 V –> Open line on corresponding line
Converter failure 220 V missing –> Open line on both detection lines
switched on 218 ... 232 V <– switched on 20 V on corresponding line
Reset 0 V <– Reset 0 V on corresponding line
OFF 0 V <– OFF 0 V on corresponding line
switched on with autom. reset <– Detector test mode with autom. reset
Terminal block X10 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
27.3 Interconnection principle
E3M220 E3M080
Detection
line 1
Detection
line 2
220VDC
24VDC
24VDC
(20V)(220V)
MS5 detectors
Detection line 1
Detection line 2