E3M070 Line module ”Interactive” (superseded by E3M071)
83
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
19.3 Special functions
Emergency operation
Alarm evaluation upon ”Emergency operation” via Emergency operation proc-
essor and ”Emergency operation” in the detector
Upon emergency alarm, control console B3Q... gives a ”combined alarm” with
flashing response indicator at the detector
Upon line short circuit and failure of the line processor there is no ”Emergency
alarm”
Mimic display output (connectors ST10) only active with emergency alarm
Line separator
Upon short circuit the part of the line which malfunctions must be separated from
the rest of the line. This is carried out by line separators integrated in the detectors,
manual call points and input/output modules (however, there are detectors without
integrated separator).
A line separator is always integrated in the manual call points and input/output mo-
dules.
According to EN54 a ”simple error” can cause the malfunction of up to 32 detectors
(i.e. install a line separator at least after every 32 detectors).