K3R071 Mimic Display board (superseded by K3R072)
210
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
49.6 Important components
4
1
2
3
5
6
7
8
9
10
11
F1
K2
X1
X48
X56
X55
X50
X49
S1
ST1
K1
ON
1
1
4
1
6
ST2
Legend:
1 48 plug-in connectors, 2-pin: 2-wire cable (cable set Z3I520 = 12 cables) to
LEDs in Mimic display
2 Connector "ST1" / "ST2": Connection of data bus via flat cable
3 Fuse 'F1' 0.4 A/T: Supply input 9...45 VDC
4 Programming switch "S1": Equipment address setting
Function Programming switch S1
No. S1-1 S1-2 S1-3 S1-4
0
Test procedure:
In this setting all outputs are activated alternating between even
and uneven numbers.
off off off off
1 Equipment address 1 on off off off
2 2 off on off off
3 3 on on off off
4 4 off off on off
5 5 on off on off
6 6 off on on off
7 7 on on on off
8 8 off off off on
"S1-1...4" are set to "off" at the factory
5 Plug-in connector "X56": Output for LED 'Operation'
6 Plug-in connector "X49": Output for 'Buzzer'
7 Plug-in connector "X50": Input for key 'Lamp test'
8 Plug-in connector "X55": Input for key 'Switch-off buzzer'
9 Plug-in terminals "K1", 4 pin: Power supply 9...45V DC
10 Plug-in terminals "K2", 6 pin: Connection of data bus instead of flat cable
11 Resistor array (assembled ex work / must be assembled only for one device)