K3I050 LON/Mimic Display converter
223
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
52.6 Important components
1
2
3
4
5
67
8
9
10
11
12
X7
S3
S4
ST2
S2
H1
X6
K1
R1
X8
F1
X9
LON
µ
C
ON
ON
1
1
1
6
RAM
EPROM
Legend:
1 Programming switch "S4":
S4-1 = off –> device 1...8 addressed flashing mode not supported
S4-1 = on –> only device 5....8 addressed flashing mode supported (if programmed)
S4-2 = unused
2 Plug-in connector "X6": Buzzer output
3 LED "H1": Fault indicator (lights up or flashes in case of fault 'LON-chip')
4 Plug-in connector "X8": Buzzer off key input
5 Plug-in connector "X9": Lamp test key input
6 Fuse "F1" 1.0 A/T: for supply input 9…45 VDC
7 Plug-in terminals "K1"; 6-pin: Module supply and LON-Bus
8 Resistor "R1" 100 : EOL (LON-Bus) to be removed, if K3I050 is not the last
device on the LON-Bus in stub line –> see also page 115
9 Key "S2": Service key (not used)
10 Flat cable header "ST2": Data bus to modules K3R071/072 (B3R051)