E3G080 Control module ”Extinguishing”
152
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
37.5.2 Control line ”Main valve”
To activate the pneumatic circuit up to max. 2A total current
Active upon ’Extinguishing command’ or ’Blocking input active’ (terminal 20)
until expiry of permissible operating time or until reset
Monitored for open line / short circuit
Upon open line / short circuit, in addition to a fault signal, an ”autom. + manual
activation blocked” signal is given
valve coil as line termination element
automatic calibration by means of maintenance key ”S4” (–> see page 156)
Also operational with ’Emergency operation E3G080’
Î Parameters can be set via AlgoWorks –> see document 005109
37.5.3 Control line ”Alarm horn”
To activate electronic alarm horns up to a max. of 2 A total current
Start of ’Active status’ selectable
Monitored for open line / short circuit according to the principle of reversed polar-
ity
Function change of alarm tone mode:
Î Until EP5: possible by combining with 'Illuminated warning panel' output (Con-
nection –> see page 158)
Î EP7F: Programmable via AlgoWorks (Connection –> see page 158)
Line termination with resistor 4k75
steady or pulsating is programmable
Î Parameters can be set via AlgoWorks –> see document 005109
37.5.4 Control line ”illuminated warning panel”
To activate illuminated warning panels up to a max. of 2A total current
immediately active upon ’Extinguishing command’ (inevitable as long as sec-
tor valve is active)
monitored for open line / short circuit according to the principle of reversed polar-
ity
Line termination with resistor 4k75
Î Parameters can be set via AlgoWorks –> see document 005109
37.6 Detection lines
37.6.1 Detection lines ”Manual activation”
for the initialization of the manual activation of extinguishing (independent of the
control unit)
generates ’Extinguishing command’ (even if the control unit malfunctions)
designed for manual call points, collective (mandatory Z-diode 5.6 V)
function ’AI pulse generator’
function ’break glass’
monitored for open line / short circuit
Max. 150 line resistance
line termination with resistor 4k75

Table of Contents

Other manuals for Siemens Cerberus CS1140

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus CS1140 and is the answer not in the manual?

Siemens Cerberus CS1140 Specifications

General IconGeneral
BrandSiemens
ModelCerberus CS1140
CategorySecurity Sensors
LanguageEnglish

Related product manuals