B3Q4.. / 560 Control terminal AlgoPilot
177
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
42.9 Connections B3Q560
3
2
1
+
+
Plug-in terminals ”orange”
K1
24V
5V
Supply
I-Bus modules
To the I-Bus modules
External key switch
only supported with control unit software ’EP4’ (V4.4x) onwards
1
2
1
Plug-in terminals ”orange”
K4
Operat. enabled
C
External operation
enabled
1
2
3
4
1
Plug-in terminals ”grey”
K5
C-Bus
B1
A1
B2
A2
1
2
3
4
1
Plug-in terminals ”orange
K6
Emergency
operation
5
24V
45V OUT
0V
F3
Fire alarm
F4
Switch off horn
1
2
3
4
5
6
+
-
+
-
Plug-in terminals ”orange
K7
F2
F1
3
28
9
10
14
15
+--+
E3X10.
Possibly additional control
terminals B3Q...
4
Supply 1
Supply 2
Terminal block
X16
4
-
12
13
7
6
2)
blue
blue
green
red
4)
serves at the same time as supply imput for the ”CI”
B3Q560
GND
-
-
3)
1) 5)
6)
1) CC-Bus must always be wired as a loop line (even with built-in control terminal AlgoPilot B3Q...)
2) Jumper must always be inserted
3) Configuration as in-/or output see jumpers X31, X32, X33, X34, Y31, Y32, Y33, Y34 on page 175
4) For application as "CI", external control terminals ("CT") are connected on K7
5) Cabling C-bus: max. 1000 m per loop with Ø 0.6 mm wire
max. 1400 m per loop with Ø 0.8 mm wire
(always including return line) for cable type (impedance adaptation) see page 175
6) "Cabling principle AlgoPilot B3Q..." –> see page 23