9 E3X102/103 Master module (supersedes E3X101)
9.1 Overview
z Main evaluating unit for the CS1140 series of fire detection control units with the
function of ”Main CPU”
Î With small systems the AlgoPilot B3Q... control console can also take over
the function of ”Main CPU”.
z Processes up to 16 I-Bus modules
z Various interfaces, control inputs, control outputs and supply outputs
z Flash-ROM 2MBx8Bit as program memory
z SRAM for user data and standard text
E3X102: 1MBx8Bit
E3X103: 2MBx8Bit
z Lithium battery for RAM buffering
z Integrated battery-charger and monitoring function unit as I-Bus module
z Integrated emergency operation electronics
z Integrated ground fault monitoring
z Card format 366.8 mm x 200 mm
9.2 Application
Processing capacity –> see document 'Planning' (008725 EP7F-Z1)
For larger systems with stations CC11..
Terminal blocks X15 and X16 (20 terminals each). With EMI protect.
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Terminal block X17 (20 terminals) Only for internal connections.
mounted on module chassis
for the connection of the prefabricated cable for battery, temperature sensor and
power unit
Battery terminals (+, -, Center tap)
Temperature sensor
mechanical coding
Card chassis
X15
X16
X17