E3X102/103 Master module (supersedes E3X101)
48
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
9 E3X102/103 Master module (supersedes E3X101)
9.1 Overview
z Main evaluating unit for the CS1140 series of fire detection control units with the
function of ”Main CPU”
Î With small systems the AlgoPilot B3Q... control console can also take over
the function of ”Main CPU”.
z Processes up to 16 I-Bus modules
z Various interfaces, control inputs, control outputs and supply outputs
z Flash-ROM 2MBx8Bit as program memory
z SRAM for user data and standard text
E3X102: 1MBx8Bit
E3X103: 2MBx8Bit
z Lithium battery for RAM buffering
z Integrated battery-charger and monitoring function unit as I-Bus module
z Integrated emergency operation electronics
z Integrated ground fault monitoring
z Card format 366.8 mm x 200 mm
9.2 Application
Processing capacity –> see document 'Planning' (008725 EP7F-Z1)
For larger systems with stations CC11..
Terminal blocks X15 and X16 (20 terminals each). With EMI protect.
– mounted on module chassis
– for the connection of the prefabricated cable to connection level, or
– for direct connection of the periphery
Terminal block X17 (20 terminals) Only for internal connections.
– mounted on module chassis
– for the connection of the prefabricated cable for battery, temperature sensor and
power unit
Battery terminals (+, -, Center tap)
Temperature sensor
mechanical coding
Card chassis
X15
X16
X17