B3R051 Parallel indicator terminal (supersedes B3R050)
200
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
47.6 Important components
F1
ST2
K2
ST1
S1
K1
1
ON
1
4
1
6
1
2
3
4
5
6
Legend:
1 Connector "ST1" / "ST2": Connection of data bus via flat cable
2 Fuse 'F1' 0.4 A/T: Supply input 9...45 VDC
3 Programming switch "S1": Equipment address setting
Function Programming switch S1
Nr. S1-1 S1-2 S1-3 S1-4
0
Test procedure:
In this setting all LEDs are activated alternating between even
and uneven numbers.
off off off off
1 Equipment address 1 on off off off
2 2 off on off off
3 3 on on off off
4 4 off off on off
5 5 on off on off
6 6 off on on off
7 7 on on on off
8 8 off off off on
"S1-1...4" are set to "off" at the factory
4 Plug-in terminals "K1", 4-pin: Power supply
5 Plug-in terminals "K2", 6-pin: Connection of data bus instead of flat cable
6 Resistor array (assembled ex work / must be assembled only for one device)