EasyManua.ls Logo

Siemens Cerberus CS1140 - E3 M070 Line Module Interactive

Siemens Cerberus CS1140
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E3M070 Line module ”Interactive” (superseded by E3M071)
82
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
19 E3M070 Line module ”Interactive” (superseded by E3M071)
19.1 Overview
z Line module for interactive detectors
z I-Bus module with line processor and independent emergency operation proces-
sor
z Designed for 1 loop line or stub line
z With 24 V supply output
z Line inputs and supply outputs protected against over voltage
z Card format 100 mm x 200 mm
z I-Bus address is set at programming switch ”S3
19.2 Key data
Addresses ...100 1)
Number of wires 2
Twisted cable necessary
Line resistance
...100
1) 2)
Line capacitance ...300 nF 1) 2)
Short-circuit proof line yes
(line separator in each manual call point and E/A module, automatic
detectors are available with or without line separator)
T-branch yes
Quiescent current at 24 V 215 mA with 100 detectors and supply output unloaded
(135 mA without detector)
Current at supply output ...500 mA / 20...30 VDC (not stabilized)
1) Limitations –> see document 1102
2) with MICC max. 1000 m from the control unit to the last detector, with RADOX
max. 2000 m
Terminal block X20 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis

Table of Contents

Other manuals for Siemens Cerberus CS1140

Related product manuals