K3R070 Mimic Display board (superseded by K3R071)
203
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
48.3 Wiring principle
Control console and Mimic Display board in the immediate vicinity
4 cable set Z3I520 (12 cables each) per K3R070
Equipment 1 Equipment 2
148 148
Data bus Data bus
AlgoPilot B3Q...
K1 ST4
K1 ST1
K3R070
ST2
K3R070
K1 ST2ST1
F12A100: 0.4 m / F12A470: 1.5 m 24 V supply
Mimic Display board separate from the control console
Parallel derivation 4 cable set Z3I520 (12 cables each) per K3R070
permissible Equipment 1 Equipment 2
148148
Data bus
Data bus
K7 ST4
K3R070
K1 K2 ST2
K3R070
K1 ST1 ST2
AlgoPilot B3Q...
Adapter Z3I350 max. 1000 m 24 V supply
Note:
– Max. 24 units B3R051 or K3R070 (also mixed) possible with max. 8 different addresses
– Remove resistor array except on one unit (–> see page 205)