E3M080 Line module ”Collective”
93
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
22 E3M080 Line module ”Collective”
22.1 Overview
z Line module for collective detectors (digital comparator) DS11, MS6, MS7,
MS9, MS24
z I-Bus module with common line processor for all 8 lines
z Various line types available (programmable via AlgoWorks) depending on the
connected detector series
z Line termination depending on programmable line type
z Short circuit can be evaluated as fault or alarm per module (Programming switch
’S4’)
z Line inputs protected against over voltage
z Card format 100 mm x 200 mm
z I-Bus address is set at programming switch ’S3’
22.2 Key data
Line type 1)
Index 'BD' + Software 4.4x
Type 1 1) Type 11 Type 3 1)
Index 'BD' or SW V4.4x
Type 2 1) Type 11 Type 13 1)
Connectable detector series MS6 / 7 / 9 / 24 / (DS11) DS11 / MS9 / 716 coll. Ex-detectors
–> Details see table ’Compatibility’ chapter 22.5
Number of detectors per line max. 25 2)
Number of wires 2
Twisted cable recommended
Line resistance
max. 250 max. 150 max. 50
Line capacitance
max. 4 µF
max. 57nF 3)
Line termination element
Index 'BD' + Software V4.4x 4)
EOL22 (Ex) Transzorb 20V EOL22 (Ex)
Index 'BD' 4) or SW V4.4x Z-Diode 18V Transzorb 20V SBE2 Ex
Line voltage –> see table ’line voltage’ chapter 22.3
Alarm current limit 45… 60 mA during AI pulse
max. 4.5 mA during AI "dark" phase
Line voltage limit 26.5... 27.7 V
Quiescent line current max. 4.5 mA
Reset time 3 sec.
Turn-on alarm delay 4.6 sec.
Fault delay 0.5 sec. ( index ’BF’ 15 sec.)
Module quiescent current at 24 V 85 mA
1) When parameterize the line types (AlgoWorks) it must be known whether the E3M080 line module is index 'BD' or older
2) Limitations –> see documents 825 and 001508
3) Details –> see document 1204
4) If an old E3M080 (<Index ’BD’) is exchanged for a new E3M080 (Index ’BD’), and the software V 4.4x is loaded in the control unit,
when using line types 1 and 3, the end-of-line elements must also be exchanged (Detection of the wrong end-of-line element is not
guaranteed)
Terminal block X20 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis