EasyManua.ls Logo

Siemens Cerberus CS1140 - E3 G091 Remote Transmission Interface

Siemens Cerberus CS1140
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E3G091 Remote transmission interface
163
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
39 E3G091 Remote transmission interface
39.1 Overview
z Interface for remote transmission equipment with several alarm criteria
z Designed for 4 channels
z Enables activation via make or break contact as well as the de-coupled activa-
tion of all channels upon ”Emergency alarm”
z Test LED for each channel (active upon activation)
z Activation upon ”Emergency alarm”
z Card format 100 mm x 100 mm
39.2 Application
Only necessary in systems with several remote alarm criteria
39.3 Key data
Voltage 20...32 VDC
Output contacts 4
Contact load 30 VA
Quiescent current at 24VDC 0 mA
max. current 100 mA
Terminal block X15 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
39.4 Important components
Y1
Y
X
S1
K1
K2
K3
K4
Y6
H3
1
2
3
4
5
11
6
TEST
H1
H2

Table of Contents

Other manuals for Siemens Cerberus CS1140