Siemens Cerberus CS1140 - Supply Wiring Principle

Siemens Cerberus CS1140
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E3H020 C-Bus Gateway
123
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
30.5 Supply wiring principle
E3H020 is placed inside the control
unit housing:
24 V Supply single wire
Jumpers 17-18, 19-20
C-Bus
CC
24VDC
CC
E3H020
X1-17...20
Supply
CT
E3X10.
E3H020 is placed outside
the control
unit housing:
24V supply must be wired as double
supply
C-Bus
24VDC
X1-17...20
Supply
CC CT
E3H020
C-Bus
CC
Autonomous
power supply
E3H020
Supply
I-Bus
E3C...
CT
K1
K1
Data communication
I-Bus
ST1
ST1
24V/5VDC
E3H020 is placed outside
the control
unit housing:
Autonomous power supply
With autonomous power supply the
E3C011 has the following configuration:
Emergency power supply provided
Symmetry monitoring active
Presence monitoring active
Battery charging active
Battery load test active
Battery integrated
I-Bus address = 1