E3G110 Emergency operation link
166
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
40.4 Important components
1
2
3
H4
H3
H2
H1
K8
K6
K4
K2
K1
K3
K5
K7
ST11
ST12
1
4
NA8.1
NA4.1
NA1.1
K1
1
4
ST1
ST2
ST3
ST4
ST6
ST8
ST5
ST7
5
4
6
7
Legend:
1 LED "H1...H4" : on when the AND operation is completed
2 Connectors "ST11 and ST12" : for distributor cable
3 Pins "NA1.1....NA8.8" : to connect the distributor cable
4 Flat cables F12A100 / F12A470 : connection to line module (must be ordered
separately)
5 Connectors ST1....ST8 : line module inputs via flat cable
6 Plug-in terminals "K1": Supply for "I-Bus" modules (for 24 V)
7 Distributor cable: for individual connection (contained in module)
40.5 Principle of interlinking
Example with 2 interactive line modules
Important:
Only detectors which belong to the extinguishing
SECTION may be connected to the lines
K1
I-Bus
CPU
B3Q440
1....4
Manual activation
interactive
detectors
ST10
E3G110
ST1
ST8
ST10K1
K1
K1
24/5V
E3M071 E3M071E3G080
Extinguishing SECTION
K1
Example with 1 collective line module
Note:
Only use E3M080 from index b/c onwards to-
gether with E3G110
K1
I-Bus
CPU
B3Q440
1....4
Manual activation
collective
detectors
ST10K1
K1
24/5V
E3M080E3G080
Extinguishing SECTION
E3G110
ST1 ST8
K1