E3X102/103 Master module (supersedes E3X101)
55
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
19 Programming switch "S2": Choice of "battery type"
To set temperature compensation according to information from the various battery
manufacturers
Possible battery variants Programming switch S2
Var. Battery manufacturer Battery model S2-1 S2-2 S2-3 S2-4
0 off off off off
1 on off off off
2 Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage
Germany)
CF 12-24 (VM 1224)
HP..-12
HP..-12
off
on off off
3 Genesis G12V120W15 on on off off
4 Sunrise
Panasonic
LCL 12V24S
LCL 12V..P
off off on off
5 Phoenix (Korea) FNC 12..0 on off on off
6 Yuasa NP..–12B off on on off
7 Sonnenschein Dryfit A212/..G5 on on on off
8 Power–Sonic PS12..0 off off off on
9 Hagen Drysafe HDS–12..0NB on off off on
10 Sonnenschein Dryfit A512/..G5 off on off on
11 ALARMCOM (FIAMM) 1)
FG... on on off on
12 off off on on
13 on off on on
14 off on on on
15 on on on on
”S2” is set to variant 11 (ALARMCOM) at the factory
9.5.1 Floating charge voltage as a function of temperature
Î see E3X101 page 44
20 Battery charging section
21 CPU section
22 Fuses
F1 630 mA/T supply 5 V/12 V
F2 63 mA/T auxiliary supply ASIC
F3 63 mA/T Control line alarm horn 1
F5, F6 2 A/T* Control line alarm horn 2
F7, F8 2 A/T* unused
F9 2 A/T* Emergency operation circuit "Silence horn"
F10 2 A/T* Emergency operation circuit "Common"
F11 2 A/T* Emergency operation circuit "Fire alarm"
F12 2 A/T* Supply "Control console AlgoPilot B3Q..." +
F13, F14 2 A/T* Supply "Control console AlgoPilot B3Q..." –
F15, F16 2 A/T* programmable control outputs "Q1...Q8"
F17...F25 0,5 A/T* Supply "Remote transmission"
F26 2 A/T* Supply "Reserve"
F27 2 A/T* programmable control inputs "I1...I4"
F28...F32 2 A/T* battery (F501 "Positive" / F502 "Negative" / F503 "Center")
F501...F503 6,3 A/T* supply 5 V/12 V
* Fuse with high breaking capacity