E3G050 Control module ”Contacts”
137
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
33.3 Important components
H1
H8
S3
S2
F1
ST1
K1
1
4
1
ON
ON
1
2
3
4
5
6
ASIC
I-BUS
Legend:
1 Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address Programming switch S3
Nr. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
"S3-1...6" are set to "off" at the factory
2 Flat cable header "ST1" (26-pin): I-Bus
3 Maintenance switch "S2": To switch on maintenance LEDs for test purposes.
In addition to the relay output, it also enables activation of the corresponding
LED (H1...H8)
S2-on = LED (H1..H8) lights if output is activated.
4 Plug-in terminals "K1": Supply for "I-Bus" modules
5 Fuse: 'F1' 0.5 A/T Module supply
6 Test LEDs 'H1...H8' at rear. Allocation of the individual LEDs –> see page 138