K3R070 Mimic Display board (superseded by K3R071)
205
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
48.5 Important components
1
2
3
4
5
6
7
X1
X48
K1
F1
S1
K2
ST1
F12A100
ST2
ON
1
Legend:
1 48 plug-in connectors, 2-pin: 2-wire cable (cable set Z3I520 = 12 cables) to
LEDs in Mimic display
2 Connector "ST1" / "ST2": Connection of data bus via flat cable
3 Fuse 'F1' 0.4 A/T: Supply input 9...45 VDC
4 Programming switch "S1": Equipment address setting
Function Programming switch S1
No. S1-1 S1-2 S1-3 S1-4
0
Test procedure:
In this setting all inputs are briefly activated in sequence.
off off off off
1 Equipment address 1 on off off off
2 2 off on off off
3 3 on on off off
4 4 off off on off
5 5 on off on off
6 6 off on on off
7 7 on on on off
8 8 off off off on
"S1-1...4" are set to "off" at the factory
5 Plug-in terminals "K1", 4 pin: Power supply 9...45 VDC
6 Plug-in terminals "K2", 6 pin: Connection of data bus instead of flat cable
7 Resistor array (assembled ex work / must be assembled only for one device)