E3I020 RS232 module
118
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
29 E3I020 RS232 module
29.1 Overview
z Optional device to E3X1.. master module and control console AlgoPilot B3Q...
z Contains 2 serial RS232 interfaces
z Function of interfaces is programmable
z For the conversion of the HCMOS level to RS232
z An interface with extended functions e.g. for telephone modems
z Both interfaces galvanically isolated and with EMI protection
z Communication and supply via flat cable
z Card format 100 mm x 160 mm
29.2 Application
Two application possibilities are provided:
a) Installation in the control unit
b) Installation at the rear of the control console AlgoPilot B3Q...
Application a)
2 RS232 interfaces from master module E3X10.
Mounted on the module chassis via card chassis immediately next to the E3X10.
(mounting space 32)
Application b)
2 RS232 interfaces from control console AlgoPilot B3Q...
screwed to the rear of the control console B3Q... and protected with a special
shielding (–> see document 1393 Installation instructions)
As module in the control unit
As accessory to AlgoPilot B3Q...
Mounting accessory Z1B020 E3I020
Terminal block X3 (20 terminals)
mounted on module chassis
for the connection of the prefab-
ricated cable to connection level,
or
for direct connection of the pe-
riphery
Card chassis
mounted on module chassis
29.3 Key data
Operating voltage 5 V from E3X10. via flat cable or B3Q... via
flat cable
Quiescent current increase E3X10. / B3Q... when
operating one E3I020
25 mA (increase on 24 V-side)