E3L030 Control module VdS (VdS module)
134
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
3 LED indicator block
yellow "Emergency operation E3L030 or E3X... or AlgoPilot B3Q..."
green "Activate unlocking"
yellow "Activate extinguishing"
red "Activate ÜE"
H2
H1
4 0 resistor "X12": For the allocation of "LED4" active when the E3L030 is in
emergency operation mode (LED4 is provided as a "spare" in FBF).
0 resistor "X12" inserted: LED 4 is active when E3L030 is in emergency
operation mode (fault)
0 resistor "X12" not inserted (factory set)
5 Flat cable header "ST1" (26-pin): I-Bus
6 Fuse: 'F31' 2 A/T Module supply (Fuse with high breaking capacity sand-
filled)
7 Plug-in terminals "K1": Supply for "I-Bus" modules
8 Programming switch "S3": Setting "I-Bus address"
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address Programming switch S3
Nr. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) 1) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
"S3-1...6" are set to "off" at the factory
1) E3L030 functions in "emergency operation" with I-Bus address 0
32.5 Special functions
Emergency operation
An alarm which occurs during system malfunction (emergency operation) can still
be handled via FBF and ÜE and FSD can also still be activated.
Function overview during ”emergency operation”
Function Emergency opera-
tion E3L030
Emergency opera-
tion CPU
FBF
Indicator ”ÜE activated”
Indicator ”LEDs 5, 6, 7, T5 operational”
Function ”Silence audible signal”
ÜE
Function ”Activate ÜE”
FSD
Function ”Activate FSD unlocking”
SST (Extinguishing standard interface)
– –
TK (Door switch control unit)