Fire Safety & Security Products 02.2005
32 E3L030 Control module VdS (VdS module)
32.1 Overview
I-Bus module for the connection of VdS peripheral equipment:
Î FBF Feuerwehr-Bedienfeld: Fire department control panel
Î ÜE Übertragungseinrichtung: Transmission device
Î FSD Feuerwehrschlüsseldepot: Fire department key cabinet
Î SST Standardschnittstelle (VdS) für fremde Lösch-Steuereinrichtung:
Standard interface (VdS) for 3rd party extinguishing activating device
Î TK Türkontakt Zentrale: Door switch control unit (door open = ÜE disabled)
z Connection line to ÜE, FSD and SST monitored
z All inputs/outputs to the peripheral equipment with EMI and over voltage protec-
tion
z Emergency operation capability
z Card format 233 mm x 200 mm
z I-Bus address is set at programming switch ”S3”
32.2 Application
z The VdS module is required for connection of the above mentioned peripheral
equipment.
z It is possible to use several VdS modules or one single VdS module for all CPUs
within a C-Bus system.
Restriction: If one single VdS module is used for all CPUs, it must not be placed
in a CI1145–station. Activation in emergency operation mode would not be pos-
sible.
Several VdS modules per CPU would be possible if separate transmission paths
are required for different detector types (automatic/manual).
z The VdS module is not FM compliant. It may be used in a ground fault moni-
tored installation, but it is not monitored itself. (For details –> see chapter 6)
z All inputs/outputs are fix allocated (exception LED4)
32.3 Key data
Line resistance for FBF
max. 5 Ω or 20 Ω per wire *
Line resistance for FSD
max. 5 Ω or 50 Ω per wire *
Line resistance for ÜE
max. 10 Ω per wire *
Line resistance for SST
max. 10 Ω per wire *
Control output load max. 40 mA with EMI protection
Quiescent current at 24 V 18 mA (Normal operating mode)
* Detail –> see page 135