E3I040 I-Bus/LON module
116
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
28.5 Important components
7
6
5
4
3
2
1
8
9
ASIC
S3
F1
ST1
H3
R60
X30
H1
H2
K1
1
4
1
ON
RAM
EPROM
S1
µ
P
LON
C
µ
Legend:
1 Jumper "X30": Ground fault monitoring 'LON-Bus'
'out' = inactive (factory setting)
'in' = active
(Details application –> see chapter 6)
2 LED "H3": inactive –> normal operation
lit or flashing –> EPROM is missing or faulty
3 Service key "S1": no function
4 Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address Programming switch S3
No. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
"S3-1...6" are set to "off" at the factory
5 Flat cable header "ST1" (26-pin): I-Bus