E3G080 Control module ”Extinguishing”
151
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
37.3 Key data for E3G080 until index ’AB’
Type of line Termi-
nals
X10–..
Line voltage
’quiescent’
(line termination with 4k75)
Monitoring
current
Line
voltage
’open line’
Line
voltage ’short
circuit’
Line
voltage
’active’
Section
Control lines
’Sector valve’
’Main valve’
1/2
2/3
without R60/61 –> 80..800 mV
without R60/61 –> 0.3...1.6 V
5 mA
880 mV
1.75 V
100 mV
200 mV
24...30 V
Control lines
’Alarm horn’
’Illuminated warning panel’
4/5
6/7
2.3 V ± 10 %
0.5 mA
3.5 V
350 mV
24...30 V *
Detection lines
’Manual activation’
’Stop/blocking button’
8/9
9/10
14.25 V ± 10 %
3 mA
15 V
1.7 V
2...10 V
Detection lines
’Loss of extinguishing agent’
’Extinguishing blocked’
12/13
14/15
2.3 V ± 10 %
0.5 mA
3.5 V
350 mV
400 mV..1.3 V
Detection line
’Extinguishing activated’
16/17
17 V **
resistor 3k3
22 V **
2.7 V **
3...14 V **
Control console for B3Q440
serial interface
18/19
Voltage cannot be measured with a voltmeter
* reversed polarity in ’active’ status
** with mains operating 29 V
37.4 Key data for E3G080 from index ’AB’ (Type FM)
Type of line Termi-
nals
X10–..
Line voltage
’quiescent’
(line termination with 4k75)
Monitoring
current
Line
voltage
’open line’
Line
voltage ’short
circuit’
Line
voltage
’active’
Section
Control lines
’Sector valve’
’Main valve’
1/2
2/3
ohne R60/61 –> 80..800 mV
mit R60/61 –> 0,3...1,6 V
5 mA
880 mV
1,75 V
100 mV
200 mV
24...30 V
Control lines
’Alarm horn’
’Illuminated warning panel’
4/5
6/7
2,3 V ± 10 %
0,5 mA
3,5 V
350 mV
24...30 V *
Detection lines
’Manual activation’
’Stop/blocking button’
8/9
9/10
14,25 V ± 10 %
4,7 mA
25 V
2,6 V
3...12 V
Detection lines
’Loss of extinguishing agent’
’Extinguishing blocked’
12/13
14/15
2,3 V ± 10 %
0,5 mA
3,5 V
350 mV
400 mV..1,3 V
Detection line
’Extinguishing activated’
16/17
17 V **
resistor
2k25
22 V **
2,7 V **
3...14 V **
Control console for B3Q440
serial interface
18/19
Spannung nicht messbar mit Voltmeter
* reversed polarity in ’active’ status
** with mains operating 29 V
37.5 Control lines
37.5.1 Control line ”Sector valve”
To activate the extinguishing valve up to a max. 2 A total current
active upon ’extinguishing released’ upon expiry of the delay period until ex-
piry of the permissible operating time or until reset
monitored for open line / short circuit
Upon open line / short circuit, in addition to a fault signal, an ”autom. + manual
activation blocked” signal is given
valve coil as line termination element
automatic calibration by means of maintenance key ”S4” (–> see page 156)
Î
Parameters can be set via AlgoWorks –> see document 005109

Table of Contents

Other manuals for Siemens Cerberus CS1140

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus CS1140 and is the answer not in the manual?

Siemens Cerberus CS1140 Specifications

General IconGeneral
BrandSiemens
ModelCerberus CS1140
CategorySecurity Sensors
LanguageEnglish

Related product manuals