E3G080 Control module ”Extinguishing”
156
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
4 Flat cable header "ST1" (26-pin): I-Bus
5 Maintenance switch "S1": Test to block all outputs
For testing of all outputs but without real activation. State 'active' is only simulated
(visible on service LEDs H1...H4) instead of real activation.
S1 on =
a) All outputs blocked. Only service LEDs light up on activation
b)
Main / and sector valve also blocked hardware wise
c) input 'extinguishing actuated' blocked but line monitoring remains
Note:
The function of switch 'S1' is equal to the blocking function via AlgoPilot
menu.
Only difference: If blocked via AlgoPilot menu, valves are not
blocked
hardware wise
6 Test LEDs "H1...H4" (Maintenance LEDs) for maintenance work
LED "H1"
sector valve active / short circuit / open line
LED "H2"
main valve active / short circuit / open line
LED "H3"
alarm horn active / short circuit / open line
LED "H4"
illuminated warning
panel
active / short circuit / open line
Function Status
LED on continuously active
LED flashes rapidly short circuit
LED flashes slowly open line / fuse blown / end-of-line resistor missing
7 Plug-in terminals "K1": Supply for "I-Bus" modules
8 Key "S4": for initialization of commissioning functions. Only effective if switch
"S1" is set to on.
Pressing "S4" has
the following ef-
fect:
a) Alignment of main / and sector valve (automatic calibration of
the monitoring current on the internal resistance of the valve
coil) Alignment of alarm horn, illuminated warning panel
b) Read in all detection lines (store what is connected to the
detection lines: end-of-line resistor, make/break contact)
c) Error diagnosis (see document 1456 EP5, 005109 EP7F
'Commissioning Extinguishing')
9 Programming switch "S2": Selectable functions in operating condition "Emer-
gency operation" (malfunction of module E3G080) (–> see page 21 ” Emer-
gency operation”)
Function Programming switch S2
S2-1 S2-2
Blocking input (terminal 20) active in emergency operation mode =
activates ”Main valve”
on
Detection line ’Extinguishing activated’ active in emergency operation
mode = ’Emergency alarm + illuminated warning panel’ active
on
Function cancelled off off
”S2-1/2” are set to ”on” at the factory
10 Fuse: "F7" 1A/F Module supply (SMD fuse can only be changed at fac-
tory)
11 Key "S5": no function