E3C011 Battery charging module (supersedes E3C010)
64
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
12 E3C011 Battery charging module (supersedes E3C010)
12.1 Overview
z For the charging and monitoring of the 24 V emergency power battery (the same
function unit is contained in the E3X10. master module
z I-Bus module with processor
z Designed for the AC/DC converter B2F020
z Temperature compensation via external temperature sensor
z Choice of functions (via maintenance PC)
emergency power available yes/no yes *
battery available yes/no yes *
charging yes/no yes *
presence monitoring yes/no yes *
symmetry monitoring yes/no yes *
automatic battery load test yes/no yes *
Fault signal delay upon mains failure 1 …30 min.
* factory setting is possibly
overwritten if E3C011 is
run via I-Bus (via Al-
goWorks)
z
Card format 100 mm x 200 mm
12.2 Application
Î see page 24
z For auxiliary batteries
z As an autonomous battery charger for AlgoPilot B3Q... control consoles installed
at a great distance
12.3 Key data
Input voltage 29.6 VDC ±2 % (B2F020)
Battery 2 x 12 V / 6...42 Ah, lead battery
(full battery recharging up to 80 % within 24 h)
Charging characteristics Can be adjusted to 16 makes of battery using programming switch ”S2”
Charging current max: 1.7 A (current limitation)
Battery monitoring Battery presence test every 55 sec
Symmetry monitoring Asymmetry > 1 V = Fault
Battery test automatic battery load test
(3 A for 10 sec once every 23 h),
Can also be activated manually via AlgoPilot B3Q... control console
EMI-protected battery line no
Low discharge protection Battery operation switches off when voltage is 21.0 V
Quiescent current 20 mA when on emergency power operation
40 mA when on mains operation without battery charging
Terminal block X17 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable for battery, temperature sensor and
power unit
Battery terminals (+, –, Center tap)
Temperature sensor
Card chassis
mounted on module chassis