EasyManua.ls Logo

Siemens Cerberus CS1140 - Current Consumption

Siemens Cerberus CS1140
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E3M220 MS5 Adapter
113
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
4 Glow lamp "H9" (65 V, 1.5 mA): 220 V ON
5 Plug-in terminals "K1": Module supply 24 V
6 4-pin female connector strip with connection cable
7 Fuse: 'F1' 1 A/F Module supply (SMD fuse can only be changed at factory)
27.5 Current consumption
24 V Quiescent
condition
both lines with 150 kend-of-line resistor
both lines with 82 kend-of-line resistor
227 mA
247 mA
Alarm status + 120 mA per line Alarm status
max. both lines short circuit 695 mA
27.6 Connections
Input Supply
Plug-in terminals
K1
End-of-line resistor 82 ... 150k
Terminal block
X10
E3M220
1
2
3
4
5
6
7
8
9
10
11
12
+
-
+
13
14
15
16
17
18
19
20
2
3
4+
1
0V
-
-
24V
+
-
Line 2
-
+
-
+
-
Line 1 / MS5
Line 2 / MS5
Important
220V
to E3M080
Please note:
- Exchange existing (82k ) end -of-line resistors for 150k end-of-line
resistors, in order to reduce the quiescent current
- Manual call points require a 10k /2 resistor, in order to activate alarm
- Line resistor up to 250
ΩΩ
ΩΩ
F1
Line termination Pos V33
Transzorb 20V
Line 1
Line termination Pos V31
Transzorb 20V
End-of-line resistor 82 ... 150k

Table of Contents