E3M080 Line module ”Collective”
95
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
22.5 Compatibility (detector <–> line type)
Incompatible
AT3
ATAN3
MS6 detectors
External response indicators with incandescent lamps
SE20 with incandescent lamp as response indicator
FES 7.5 detectors
220 V detectors
Line type 11 Compatible
Î Line termination with Transzorb 20 V AlgoRex detectors:
DO110x , DT110x , DM110x, DC1192 Standard application, also for Ex detectors via
DC1192 Older detectors:
MS716 , MS9 , MLK20 , T2416/18 , D2417 , SE22, AT4x, AT5x without SE2
Base: Z74*, Z74A*, Z90, Z94, Z96
* Limitations: Z74 and Z74A only from the 1988 model (year index W)
D900 only from the 1983 model (year index R)
–> if in doubt use line type 1
Ex detectors (without restrictions)
used via DC1192 with SB3: DO110x Ex, DT110x Ex
F911, D901, D921 with base Z91C/Z94C
D2401 Ex, S2406Ex
F6A Ex, D6A Ex
Line type 1 Compatible
Î Line termination with EOL22(Ex) AlgoRex detectors:
DLO1191, (with mixed lines also DO110x, DT110x, DM110x, DC1192) for older detectors, also for mixed lines (newer
and older detector types) Older detectors:
MS6* , MS7*, MS9 , MS24 , SE20* , SE22 , MLK20, AT4x, AT5x, SE2
Base electronics: Z70, Z72, Z72A, Z74, Z74A, Z90, Z94, Z96
Note:
replaces line type 2
Limitations: For MS6 and MS7 note the listed detector types and applications as stated
under 'Incompatibility'
Î Not permissible with line type 2: DO110x, DLO1191
Line type 3 (Ex) For Explosion hazard area with limitations:
Only with safety barrier SB2 Î Via safety barrier SB2 and line termination
EOL22 (Ex)
Only without short to earth monitoring
For Ex detectors with limitations Only 1 Ex-line per installation
or
Note:
replaces line type 13
several Ex lines, however with a common ground connection off all SB2s to the con-
trol unit, whereby the ground conductor must have a min. cross-sectional area of
1.5 mm
2
and be no longer then 50 m
Î Comply with the local safety regulations
Compatible
DO110x Ex, DT110x Ex
F911, D901, D921 with base Z91C, Z94C
D2401 Ex, S2406 Ex
F6A Ex , D6A Ex
Î Not permissible with line type 13: DO110x Ex