E3I040 I-Bus/LON module
114
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
28 E3I040 I-Bus/LON module
28.1 Overview
z Converter I-Bus to LON-Bus
z Up to 32 LON-Bus devices connectable
z With 24 V supply output
z Selectable ground fault monitoring, detected via master module E3X10. (for ap-
plication details see chapter 6)
z Board format 100 mm x 200 mm
z I-Bus address is set at programming switch ”S3”
z Only one module per station possible
28.2 Application
Required for all LON applications within CS1140, such as:
– LON-I/O p.c.b. K3I110
– LON/Mimic Display converter K3I050 with Mimic display drivers K3R071/072 (or
panels B3R051)
– Floor panels B3Q580
– Fire Brigade Terminals B3Q590/595
Terminal block X2 (20 terminals)
– mounted on module chassis
– for the connection of the prefabricated cable to connection level, or
– for direct connection of the periphery
Card chassis
– mounted on module chassis
28.3 Key data
Number of devices per line ...32
LON-Bus: number of wires
cable type
max. cable length
2
twisted (10 twists per m)
– standard cable twisted 0.8mm Ø unshielded as ’stub line’ ...1000m
– same but as ’free topology’ 1) .....500m
– using MICC-cable .....700m
– using MICC-cable as ’free topology’ 1) .....300m
– using special cable Belden 85102 or 8471 ...2700m
LON-Bus: connection twisted cable necessary
Typical current consumption (24 V) 15 mA without load on output (pin 9/10)
Rating supply output (pin 9/10) max. 860 mA / 20....29.6 V
1) Free topology see chapter 28.4.2