K3R072 Mimic Display board (supersedes K3R071)
212
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
50 K3R072 Mimic Display board (supersedes K3R071)
50.1 Overview
z Option to control console AlgoPilot B3Q..., or to LON/Mimic Display converter
K3I050
z 2x24 outputs for LED activation for Mimic Display panels, or not monitored relay
contacts (K3G060)
z 2 control outputs for local ’Buzzer’ and ’LED operation’
z 2 inputs for ’Switch-off buzzer’ und ’Lamp test’
z The lamp test is integrated in menu function AlgoPilot
z Individual allocation of the individual outputs
z Max. 24 units, however max. 8 addresses
z Communication is via a special serial bus
z Line and device not monitored
50.2 Application
The Mimic Display board is built into the mimic panel housing.
Connection to LED via flat cable F50F410 (50-wire, 24 red LEDs, cable length
1 m, must be ordered separately)
The relay card K3G060 can be connected instead of LEDs
Line length data bus AlgoPilot –> K3R072 max. 1000 m
Connection line
Data bus: via flat cable or 6-wire cable
Supply 24 V: via 3-wire cable
Short-circuit proof in-/outputs only for inside housing appli-
cation
Synoptic display panel housing AlgoPilot
max. permissible length of the data bus 1000 m
1) LED 1…24 –> wires 49+50 for 'LED operation'
2) LED 25…48 –> wires 49+50 unused
3) Key 'Switch-off buzzer'
4) Key 'Lamp test'
5) Buzzer
1
2
3
4
5
6
6) Use Z3I520
These in-/outputs can be in
parallel with other K3R072 if
located in same cabinet
50.3 Key data
Operating voltage 9..45 VDC
Current consumption at 24 V
at 9 V
at 45 V
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA