K3R070 Mimic Display board (superseded by K3R071)
202
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
48 K3R070 Mimic Display board (superseded by K3R071)
48.1 Overview
z Option to control console AlgoPilot B3Q...
z Enables the activation of LEDs for Mimic display panels
z Unit with 48 short-circuit proof outputs on connectors
z Individual allocation of the individual outputs
z Max. 8 pcs. K3R070 per control console B3Q... possible
z Communication is via a special series bus (not monitored)
z The lamp test is integrated in menu function AlgoPilot B3Q...
Positioning
In the vicinity of the control consoles AlgoPilot B3Q... or up to 1000 m away.
Installation
The Mimic Display board is built into the Mimic Display panel housing.
connection to Mimic Display LED by means of 2-wire cable with connector, avail-
able as cable set Z3I520 containing 12 pieces
Connection line
Data bus: via flat cable or 6-wire cable
Supply 24 V: via 3-wire cable
Synoptic display panel housing max. 1000 m
48.2 Key data
Operating voltage 9..45 VDC
Current consumption at 24 V
at 9 V
at 45 V
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA