E3G080 Control module ”Extinguishing”
153
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
37.6.2 Detection line ”stop/blocking button”
for external blocking of activation of extinguishing via special push button or door
switch (alarm resistor 1k2 or Z-Diode 5.6 V)
can be used as required for function ’Stop button’ or ’Blocking button’
monitored for open line / short circuit
Upon open line / short circuit, in addition to a fault signal, an 'autom. + man. acti-
vation blocked’ signal is given
Max. 150 line resistance
Line termination with resistor 4k75
Î Parameters can be set via AlgoWorks –> see document 005109
37.6.3 Detection line ”Loss of extinguishing agent”
for signal transmitters such as cylinder weighing device, manometer etc. (if u-
sed)
select as required for make or break contacts with alarm resistor 1k2
monitored for open line / short circuit
Max. 150 line resistance
line termination with resistor 4k75
Î Parameters can be set via AlgoWorks –> see document 005109
37.6.4 Detection line ”Extinguishing blocked”
for signal transmitters of the blocking mechanism (if used)
select as required for make or break contacts with alarm resistor 1k2
monitored for open line / short circuit
Max. 150 line resistance
Line termination with resistor 4k75
Î Parameters can be set via AlgoWorks –> see document 005109
37.6.5 Detection line ”Extinguishing activated”
for genuine confirmation of release of extinguishing agent
for signal transmitters such as pressure switches (pressostats) or activating me-
chanisms (if used)
Active status generates ”Extinguishing activated” (activates alarm horn and illu-
minated warning panel (if not already active)
if the active status follows within <10 sec of reset, a fault signal is also activated
select as required for make or break contacts with alarm resistor 1k2
monitored for open line / short circuit
Max. 150 line resistance
Line resistance with 4k75 resistance
Î Parameters can be set via AlgoWorks –> see document 005109