E3X101 Master module (superseded by E3X102/103)
37
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
8 E3X101 Master module (superseded by E3X102/103)
8.1 Overview
z Main evaluating unit for the CS1140 series of fire detection control units with the
function of ”Main CPU”
Î With small systems the AlgoPilot B3Q... control console can also take over
the function of ”Main CPU”.
z Processes up to 16 I-Bus modules
z Various interfaces, control inputs, control outputs and supply outputs
z EPROM as program memory
z RAM depending on application
z Lithium battery for RAM buffering
z Integrated battery-charger and monitoring function unit as I-Bus module
z Integrated emergency operation electronics
z Integrated ground fault monitoring (not contained in E3X100)
z Card format 366.8 mm x 200 mm
8.2 Application
Processing capacity see document ’Planning’ (1076 EP5, 004595 EP7F-Z1),
for larger systems with stations CC1142 or CC1143.
According to system size (table of quantities) choose the corresponding
EPROM+RAM set:
– for CC1142 –> CCQ00xxx (EPROM set 2x 512Kx8Bit)
Z3S070 (RAM set 2x 512Kx8Bit)
– for CC1143 –> CCW00xxx (EPROM set 2x 512Kx8Bit)
Z3S070 (RAM set 2x 512Kx8Bit)
K3N010 (RAM board 1x 1MB)
Recommended EPROMs: 27C040, 27C4001 (512Kx8Bit, 100 ns, DIP32)
Terminal blocks X15 and X16 (20 terminals each). With EMI protect.
– mounted on module chassis
– for the connection of the prefabricated cable to connection level, or
– for direct connection of the periphery
Terminal block X17 (20 terminals) Only for internal connections.
– mounted on module chassis
– for the connection of the prefabricated cable for battery, temperature sensor and
power unit
Battery terminals (+, –, Center tap)
Temperature sensor
mechanical coding
Card chassis
X15
X16
X17