31 E3L020 Control module ”I/O”
31.1 Overview
z Control module for 16 control inputs/outputs
z Driver output or control input as required
z I-Bus module
z Inputs/outputs with voltage surge and EMI protection
z Individual function allocation of inputs/outputs
z Ground fault monitoring, detected via master module E3X10. (for application de-
tails see chapter 6)
z Card format 100 mm x 200 mm
z I-Bus address is set at programming switch ”S3”
31.2 Key data
Control outputs 16, load capacity up to 40 mA (24 VDC)
Control inputs 16 via volt-free contacts
Quiescent current at 24 V 22 mA
Terminal block X10 (20 terminals)
– mounted on module chassis
– for the connection of the prefabricated cable to connection level, or
– for direct connection of the periphery
Card chassis
– mounted on module chassis
31.3 Important components