E3L020 Control module ”I/O”
129
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
31 E3L020 Control module ”I/O”
31.1 Overview
z Control module for 16 control inputs/outputs
z Driver output or control input as required
z I-Bus module
z Inputs/outputs with voltage surge and EMI protection
z Individual function allocation of inputs/outputs
z Ground fault monitoring, detected via master module E3X10. (for application de-
tails see chapter 6)
z Card format 100 mm x 200 mm
z I-Bus address is set at programming switch ”S3
31.2 Key data
Control outputs 16, load capacity up to 40 mA (24 VDC)
Control inputs 16 via volt-free contacts
Quiescent current at 24 V 22 mA
Terminal block X10 (20 terminals)
mounted on module chassis
for the connection of the prefabricated cable to connection level, or
for direct connection of the periphery
Card chassis
mounted on module chassis
31.3 Important components
F2
F17
F18
F1
S3
ON
1
1
4
K1
ON
S2
F19
ST1
ASIC
I-BUS
H1
H16
1
2
3
4
5
6
7
8
9