EasyManua.ls Logo

Siemens Cerberus CS1140 - Connections

Siemens Cerberus CS1140
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
K3I110 LON I/O p.c.b.
230
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
53.7 Connections
K3I110
1
2
programmable
control output 1
LED 1
2
3
4
+
Plug-in terminals
K1
Supply 9...45VDC
1
R1
3
4
LED 2
R2
1
2
LED 3
R3
3
4
LED 4
R4
max. 30V / 1A
0V
F1
24V supply
to other LON device
Plug-in terminals
X57
Plug-in terminals
X56
not used
LON-Bus
5
6
R1
1
2
LED 15
R15
3
4
LED 16
R16
Plug-in terminals
X63
1
2
3
4
1
2
3
4
Plug-in terminals
X32
Plug-in terminals
X31
1
2
3
4
Plug-in terminals
X37
max. 30V / 1A
4k75
1
2
3
4
Plug-in terminals
X38
4k75
1k87
Application
Contact
NO NC
Monitored on
short circuit
A
B
C
D
X
X
X
X
X
X
Connection of external contact
A
B
C
D
4k75
4k75
1k87
Earth
from E3I040 or from previous LON device
programmable monitored
control input 1
programmable
control output 2
programmable
control output 3
programmable
control output 4
programmable
control output 15
programmable
control output 16
programmable monitored
control input 2
programmable monitored
control input 3
programmable monitored
control input 4
programmable monitored
control input 13
programmable monitored
control input 14
programmable monitored
control input 15
programmable monitored
control input 16
*
*
*
*
* Set the protective circuit according to the tool settings (Default no supervision)