B1F120 Converter
73
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
14.3 Important components
115VAC
230VAC
1
2
3
4
5
6
7
8
Î Check mains voltage setting before commissioning
DANGER
The converter is supplied by the factory at 230 VAC.
To switchover to 115 VAC remove metal shield (remove screws ) and then
plug in jumper at the "115 VDC" pin.
Legend:
1 Mounting flange
2 Mounting screws for metal shield
3 Clamp to fasten the mains cable
4 Power supply (Mains)
5 unused
6 24 V load (24 V)
7 Mounting screws for metal shield
8 Jumper for switchover 115 VAC / 230 VAC
14.4 Connections
B1F120
+
-
E
N
L
Input voltage
(115VAC) 230VAC / 50....60Hz
max. 140VA
Output voltage
24....28VDC / max. 3A
Mains
24V load
Opt
Sd
-
- S
+ S
+
Jumpers inserted at factory (essential)
DANGER