K3G060 Relay card
217
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
51 K3G060 Relay card
51.1 Overview
z Option to Mimic Display board K3R072
z 2 K3G060 can be connected to each K3R072
z Card not monitored
z 24 volt-free relay-make contacts
z Contacts not monitored
z Contacts can be individually connected via jumper to externally supplied V+ or
V– potential
51.2 Key data
Operating voltage 9...45 VDC
Quiescent current at 24 V
45 V
all relays de-energized 9 V
6 mA
6 mA
7 mA
Max. current 24 V
45 V
all relays energized 9 V
90 mA
50 mA
270 mA
Relay 24 x 1 NO contact
Contact load 30 VDC / 1 A
Housing supplied by customer
24 Relay outputs
24 Relay outputs
51.3 Wiring principle
Relay outputs
external potential
(V+/V–)
Data bus
ST1 or K2
external potential
(V+/V–) Relay outputs
24V
Data bus
K1
K3G060
K1
K3R072
ST1
ST11
K2
0,25m
124
ST12
0,25m
K1
K3G060
ST1
K2
124
K3
K3
ST1
Datenbus
K2
Data bus
Data bus relay activation Data bus relay activation