E3G080 Control module ”Extinguishing”
155
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
37.9 Important components
F11
F13
F14
F16
1
2
3
4
5
6
R61
R60
S3
ST1
S1
S2
H1
H2
H3
H4
7
8
S4
K1
9
10
11
S5
H5
12
13
X2
R151
14
F7
ON
1
ON
1
4
ASIC
I-BUS
µ
P
ON
Legend:
1 Fuses: "F11, F13, F14, F16" 2 A/T Main / sector valve / alarm horn / illu-
minated warning panel (Fuses with high breaking capacity, sand-filled)
2 Resistors "R60/61": Choice of internal resistor sector for the main/sector valve
Two areas can be selected for the monitoring of the valves by inserting or remov-
ing resistors. R60 (71k5) is for the sector valve and R61 (71k5) for the main valve.
R60/61 are inserted at the factory.
– Valve coil 16...160 Ω = R60/61 removed
– Valve coil 161...320 Ω = R60/61 inserted
3 Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address Programming switch S3
Nr. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
"S3-1...6" are set to "off" at the factory