K3R071 Mimic Display board (superseded by K3R072)
207
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
49 K3R071 Mimic Display board (superseded by K3R072)
49.1 Overview
z Option to control console AlgoPilot B3Q... or to LON/Mimic Display converter
K3I050
z Enables the activation of LEDs for Mimic display panels
z 48 short-circuit proof outputs on connectors for LED activation
z 2 control outputs for local ’Buzzer’ and ’LED’ operation
z 2 inputs for ’Switch-off buzzer’ and ’Lamp test’
z The lamp test is integrated in menu function AlgoPilot
z Individual allocation of the individual outputs
z Max. 24 units, however max. 8 addresses
z Communication is via a special serial bus
z Line and device not monitored
49.2 Application
The Mimic Display board is built into the Mimic Display panel housing.
Connection to Mimic Display LED by means of 2-wire cable with connector, a-
vailable as cable set Z3I520 containing 12 pieces
Line length data bus AlgoPilot –> K3R071 max. 1000 m
Connection line
Data bus: via flat cable or 6-wire cable
Supply 24 V: via 3-wire cable
Short-circuit proof in-/outputs only for inside housing appli-
cation
Synoptic display panel housing AlgoPilot
max. permissible length of the data bus 1000 m
1) LED 1…48
2) Key 'Switch-off buzzer'
3) Key 'Lamp test'
4) Buzzer
5) LED operation
These in-/outputs can be in
parallel with other K3R071 if
located in same cabinet
1
2
3
4
5
49.3 Key data
Operating voltage 9..45 VDC
Current consumption at 24 V
at 9 V
at 45 V
quiescent 40 mA
max. 140 mA
quiescent 80 mA
max. 330 mA
quiescent 30 mA
max. 90 mA