B3Q6.. / 565 Control terminal AlgoPilot
180
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
43.3 Application
z Remote location for the AlgoPilot:
– either with own local power supply or
– 24 V supplied from the control unit
z Option 9 V battery:
– Allows fault indication upon total failure of power supply (mains + battery) –>
see page 183
z According to application choose the corresponding Flash program file:
Terminal utilization as
Control terminal ’CT’ Parallel control terminal ’CA’ Control terminal and main CPU com-
bined ’CI’
B3Q660
B3Q670
B3Q680
B3Q685
CTX00xxx international 1) CAX00xxx international CIX00xxx international
B3Q565 CTYT1xxx China simplified 1)
CTYTExxx China traditional
CTYTLxxx Korea standard
CTYT5xxx Thailand
CAYT1xxx China simplified
CAYTExxx China traditional
CAYTLxxx Korea standard
CAYT5xxx Thailand
CIYT1xxx China simplified
CIYTExxx China traditional
CIYTLxxx Korea standard
CIYT5xxx Thailand
1) Default at factory programmed
The Flash program files are available from OSS.
43.4 Functions
Interfaces
– C-Bus –> Plug-in terminals ’K5’
– I-Bus –> Connector ’ST1’
– 2 x RS232 –> Connector ’ST2’
– Parallel indicator panel B3R051/K3R071/072 –> Connector’ST4’
– Emergency operation circuit –> Plug-in terminals ’K6’
Control inputs
– external key switch (see Operation enabled)
– monitoring of autonomous power supply
– monitoring of Plexiglas door (open / closed)
Operation enabled
– this is normally done via password at the keyboard
– An integrated key switch, (photoelectric) is available as an option which can also
be used to lock the Plexiglas door (if used).
– operation can also be enabled by an external key switch