E3C010 Battery charging module (superseded by E3C011)
61
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
3 Programming switch "S2": Set battery type
To set temperature compensation according to information from the various battery
manufacturers.
Possible battery variants Programming switch S2
Var. Battery manufacturer Battery model S2-1 S2-2 S2-3 S2-4
0 off off off off
1 on off off off
2 Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage
Germany)
CF 12-24 (VM 1224)
HP..-12
HP..-12
off
on off off
3 Genesis G12V120W15 on on off off
4 Sunrise
Panasonic
LCL 12V24S
LCL 12V..P
off off on off
5 Phoenix (Korea) FNC 12..0 on off on off
6 Yuasa NP..–12B off on on off
7 Sonnenschein Dryfit A212/..G5 on on on off
8 Power–Sonic PS12..0 off off off on
9 Hagen Drysafe HDS–12..0NB on off off on
10 Sonnenschein Dryfit A512/..G5 off on off on
11 ALARMCOM (FIAMM) 1)
FG... on on off on
12 off off on on
13 on off on on
14 off on on on
15 on on on on
”S2” is set to variant 11 (ALARMCOM) at the factory
1) available from index 'CB' onwards
Î Floating charge voltage as a function of temperature, or for diagrams of the vari-
ous types of battery see page 44
4 Flat cable header "ST1" (26-pin): I-Bus
5 LED indicator block "Power supply status"
yellow "Power supply fault"
green "Mains operation"
yellow "Battery fault"
H501
H502
yellow unused
Indicators vary in meaning according to application:
a) Battery operation
and symmetry moni-
toring
LED ”Power supply fault
Input voltage > 31.0 V –> power unit malfunction
Battery voltage > 29.5 V or < 25 V –> charger malfunction
Charger malfunction
Charger shut down (via software function)
Temperature sensor open line / short circuit
Temperature sensor measures > 55 °C
EEPROM check sum error
LED ”Power on”
Input voltage > 28.5 V
LED ”Battery fault
Battery voltage < 23 V
Asymmetry > 1.0 V or fuse F503 blown
Possibly cell short circuit
Open line to battery or fuse F501 / F502 blown
Autom. test to indicate battery presence negative
Autom. battery load test negative
b) Battery operation
without symmetry
monitoring
LED ”Power supply fault
Input voltage > 31.0 V –> power unit malfunction
Battery voltage > 29.5V or < 25 V –> charger malfunction
Charger malfunction
Charger shut down (via software function)
Temperature sensor open line / short circuit
Temperature sensor measures > 55 °C
EEPROM check sum error
LED ”Power on”
Input voltage > 28.5 V