E3H020 C-Bus Gateway
125
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
3 EPROM plug-in spaces EVEN / ODD: Software
4 RAM plug-in spaces (static RAM)
CK1142:
8 pcs. 256Kx8Bit / Pos. D11… D18 or
4 pcs. 512Kx8Bit / Pos. D11, D12, D15, D16 (ex works)
CK1143:
8 pcs. 512Kx8Bit / Pos. D11… D18
5 Connector (96-pin) "ST10": for interface extension
6 Connector "ST2" (14-pin): "Asynchronous" interface (TTL) to K1D012,
K1D081, K1D121 or K1H021 and AlgoWorks service port
7 Key "S4": Reset
8 Programming switch "S3": "Station address" setting
To set the station address and whether with or without autonomous power supply
Programming switch S3 Function
1 2 3 4 5 6 7 8 9 10
EP5:
Station address 16
off off off off
on
EP7F:
unused (via SW)
off off off off off
used on
E3C011
unused off
9 Double flat cable header "ST1" (26-pin):I-Bus from E3C011 (if used)
10 3-pin female connector with 2-pin jumper
11 4-pin female connector
12 Plug-in terminals "K1": Supply line from E3C011 (if used)
13 Plug-in terminals "K2"
14 Lithium battery 3 V / 70 mAh: RAM buffering and clock supply
– Data safeguarded: minimum 2 weeks, typical >100 days
– maintenance free
15 Resistors to modify the C-Bus impedance:
Position
Impedance value 110,
e.g. for G51 0.6mm Ø
Impedance value 50,
e.g. for MICC
R180 / 183
402 182
R173 / 174 / 177 / 178
110 49.9
Impedance adaptation only required if C-Bus line is > 100m. For other impedance
values than 110 or 50 –> see document 1594.
16 Programming of "X1":
Use of E3H020
0 -resistors
”CK” + supply from control unit (Input) (X1-17.. 20) X15 + X16 + X17 + X18
”CK” + autonomous supply (Output) (X1-17.. 20) Y15 + Y16 + Y17 + Y18
17 Programming switch "S5": Interfaces RS232-1 and RS232-2, choice of path
via header "ST2" (external modem) or via terminal block "X2" (internal mo-
dem).
Programming switch S5 Interface Application
1 2
internal modem via terminal block ”X2” off RS232-1
external modem via header ”ST2”
on
internal modem via terminal block ”X2” off RS232-2
(Service port)
external modem via header ”ST2”
on
Set to ”off” at factory