E3G060 Control module ”monitored” (Part No 460514)
140
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
34.4 Important components (Part No 460514)
H1
H6
F19
S2
ST1
S3
S6
K1
1
4
1
1
ON
ON
ON
1
2
3
4
5
6
7
8
ASIC
I-BUS
F1
F12
Legend:
1 Emergency operation –> Programming switch "S6": Allocation activation by
"Emergency operation mode"
If required, the 6 control lines can also be activated even if an alarm is given during
system malfunction (emergency operation). This function can be selected for each
control line via the "S6" programming switch.
Affiliation: "S6-1" = Control line 1...
"S6-6" = Control line 6
"OFF" Position = Control line is activated in "Emergency operation mode"
2 Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address Programming switch S3
Nr. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
"S3-1...6" are set to "off" at the factory