E3G070 Control module ”universal”
148
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
Legend:
1 0 resistors
"Y12" = Remote transmission alarm as make contact (factory setting)
"X12" = Remote transmission alarm as break contact
"Y13" = Remote transmission fault as break contact (factory setting)
"X13" = Remote transmission fault as make contact
2 Jumper "X60": Ground fault monitoring 'control unit'
'out' = inactive (factory setting)
'in' = active (for application details –> see chapter 6)
3 Programming switch "S3": "I-Bus address" setting
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus devices.
Function / I-Bus address Programming switch S3
Nr. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
"S3-1...6" are set to "off" at the factory
4 Flat cable header "ST1" (26-pin): I-Bus
5 Maintenance switch "S2": to switch on maintenance LEDs for test purposes.
In addition to driver output, enables the corresponding LED (H1... H11) to be
activated
S2-on = LED (H1… H11) lights if output is activated.
6 Plug-in terminals "K1": Supply for "I-Bus" modules
7 Fuse 'F1' 5 A/T Module supply
8 Fuses: 'F2, F3' 0.63 A/T Supply output
'F4, F5' 0.25 A/T Control outputs / inputs
'F6...F9' 2 A/T* Control lines for alarm devices
* Fuse with high breaking capacity (sand-filled)
9 Connector "K2" to fit cable set Z3I390 for the remote transmission equipment
10 Test LEDs H1...H11 at rear. Allocation of the individual LEDs see page 149