E3X100 Master module (superseded by E3X101)
29
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
Emergency operation
An alarm which in the event of a system malfunction is signaled at the control pa-
nel as a ”combined alarm” (no location details). This is achieved by the emergency
operating circuit permanently integrated in the system.
Emergency operation circuit at C-Bus level
Covers the functions ”Combined alarm” and ”Silence alarm horns”
Requires 3 additional wires between E3X100 and B3Q...
Emergency operation circuit at I-Bus level
Covers the functions ”Emergency alarm” and ”Silence alarm horns” on the vari-
ous I-Bus modules
Integrated in the I-Bus flat cable (for this purpose 2 lines lead via all modules to
the E3X100)
Emergency alarm
In the event of simultaneous alarm and malfunction of the master module and /
or control console B3Q... (Emergency alarm) the alarm signal is reduced as fol-
lows:
Combined alarm at control console B3Q... level (visual and buzzer),
Alarm horns are activated and can be silenced at control console B3Q... level
Remote alarm is activated via contact at the CPU.