E3X101 Master module (superseded by E3X102/103)
43
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
LED ”Battery fault
Battery voltage or external voltage < 23 V or > 31.0 V
Autom. presence test (external voltage) negative or fuse F501 / F502
blown
LED ”Power supply fault
Input voltage > 31.0 V –> power unit malfunction
EEPROM check sum error
LED ”Power on”
Input voltage > 28.5 V
d) Operation without
battery or external
voltage
LED ”Battery fault
no function
19 Programming switch "S3": Choice of "I-Bus address battery charger"
To set I-Bus address for the Function unit ”Charge /monitor battery. This unit is
an I–Bus user (as e.g. line module) and must have an individual address (number).
This is set on programming switch ”S3”.
Maximum 16 I-Bus devices
Function / I-Bus address Programming switch S3
No. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
”S3-1...6” are set to ”off” at the factory
20 Programming switch "S2": Choice of "battery type"
To set temperature compensation according to information from the various battery
manufacturers
Possible battery variants Programming switch S2
Var. Battery manufacturer Battery model S2-1 S2-2 S2-3 S2-4
0 off off off off
1 on off off off
2 Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage
Germany)
CF 12-24 (VM 1224)
HP..-12
HP..-12
off
on off off
3 Genesis G12V120W15 on on off off
4 Sunrise
Panasonic
LCL 12V24S
LCL 12V..P
off off on off
5 Phoenix (Korea) FNC 12..0 on off on off
6 Yuasa NP..–12B off on on off
7 Sonnenschein Dryfit A212/..G5 on on on off
8 Power–Sonic PS12..0 off off off on
9 Hagen Drysafe HDS–12..0NB on off off on
10 Sonnenschein Dryfit A512/..G5 off on off on
11 ALARMCOM (FIAMM) 1)
FG... on on off on
12 off off on on
13 on off on on
14 off on on on
15 on on on on
”S2” is set to variant 11 (ALARMCOM) at the factory
1) available from index ’AA' onwards