E3X101 Master module (superseded by E3X102/103)
45
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
23 Fuses
F1 630 mA/T supply 5 V/12 V
F2 63 mA/T auxiliary supply ASIC
F5, F6 2 A/T* Control line alarm horn 1
F7, F8 2 A/T* Control line alarm horn 2
F9 2 A/T* unused
F10 2 A/T* Emergency operation circuit "Silence horn"
F11 2 A/T* Emergency operation circuit "Common"
F12 2 A/T* Emergency operation circuit "Fire alarm"
F13, F14 2 A/T* Supply "Control console AlgoPilot B3Q..." +
F15, F16 2 A/T* Supply "Control console AlgoPilot B3Q..." –
F17...F25 0,5 A/T* programmable control outputs "Q1...Q8"
F26 2 A/T* Supply "Remote transmission"
F27 2 A/T* Supply "Reserve"
F28...F32 2 A/T* programmable control inputs "I1...I4"
F501...F503 6,3 A/T* battery (F501 "Positive" / F502 "Negative" / F503 "Center")
* Fuse with high breaking capacity