Z3I040, Z3I120, Z3I130 Surge protector set (superseded by Z3I041, Z3I121)
75
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
Function of the fuse
Essential to interrupt the mains lead after spark over of the surge protector.
Î Only use slow-blow fuses with ”high breaking capacity”. Depending on the fuse
in the mains lead, use fuses between 6 A and 10 A.
Surge protector cartridges (UCV...)
The plug-in surge protector cartridges model UCV... consist of an inert gas-filled,
high-performance surge protector with zinc oxide varistor connected in parallel.
Inspection and replacement:
Make a visual check when servicing the control unit. Preventive replacement of
the UCV is not necessary
brown or black discoloration of the porcelain body = defective UCV