Planning the networking of the stations
8
100 | 242
8.2 License keys
↑ License keys are needed to enable ↑ stations for network functions. Stations
which communicate with a ↑ management station with SintesoView and/or
↑ BACnet third-party product must have a license key installed.
A maximum of 2 management stations can be connected per ↑ SAFEDLINK
network.
The following license keys are available:
Function
License key from
MP5
License key up to
MP4
↑ BACnet for Siemens management
station
Possible without L2
SintesoView S1 L1
Sinteso Touch PC (in conjunction with
FT2080)
3
S2 --
BACnet third-part product (supervision
only)
S1 --
BACnet third-party product (supervision
and basic control)
S2 --
BACnet third-party product (supervision
and full control)
S3
2
--
Sinteso Mobile S3
2
--
For enabling the corresponding
SIGMASYS site size
1
S7 to S12 L3 to L7
1
You will find detailed information on the license keys for the FG2020 in technical
manual A6V10281424.
2
Backward compatible with license key (L2)
3
'Sinteso Touch PC' function does not apply to license key (L2)
Each next-higher license key is backward compatible.
station which communicates via
products must be enabled with a ↑ license key.
visibility as the connected '
therefore gain global visibility with SintesoView in a networked ↑ site. To do so,
the license key must be installed in a ↑ 'Station' with global visibility and
connected to SintesoView.