Planning the networking of the stations
Remote access to the extended network with GAP
8
124 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
1 Internal FCnet/SAFEDLINK sub-net
2 Router station in the FCnet/SAFEDLINK sub-net
3 Firewall
4 External network
5 External management station
8.14 Remote access to the extended network with GAP
The following prerequisites must be met:
The management stations have access via the firewall and GAP.
All stations in the extended network can be reached. The GAPs must be
connected to the FCnet/LAN.
The GAP is configured as a DHCP server for the purpose of connecting to
SintesoWorks via FCnet/LAN.
The following routes to the management stations (11) are configured using
SintesoWorks:
Routes in the GAP
Route via firewall:
Target address: 10.169.29.0, network mask: 255.255.255.0, gateway:
192.168.100.2
Routes in the Ethernet sub-net
Route via GAP
Target address: 10.169.29.0, network mask: 255.255.255.0, gateway:
192.168.100.1
Figure 56: Example: External access to extended network via GAP