EasyManua.ls Logo

Siemens FS20 - Guidelines for SAFEDLINK Networking

Siemens FS20
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Planning the networking of the stations
G
uidelines
8
129 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
8.16.1.2 Degraded mode with extended networking
In addition to the guidelines for SAFEDLINK networking, the following must be
noted for the degraded mode characteristics of extended networking:
If a
'
Station
' is in '
De
graded mode
' and has a '
Degraded FIRE ALARM
', all
'Stations' on the same sub-net generate a 'Degraded FIRE ALARM'. The
'Stations' in other sub-nets which are networked via 'FCnet/LAN' do not generate
a 'Degraded FIRE ALARM'.
'RT' and 'External sounder'
Because the 'RT' has the global 'Visibility', the 'Degraded FIRE ALARM' is
always activated by a 'RT'.
An 'External sounder' has the 'Visibility' 'Station' as standard and is therefore
not activated by a 'Degraded FIRE ALARM' from another sub-net.
You can change the behavior of the 'External sounder' element by extending the
'Visibility' of the 'External sounder' element to include all 'Stations' on the other sub-
nets or by configuring the global 'Visibility'.
An alarm signal can only be switched off within a SAFEDLINK sub-net in
'Degraded mode'. If, for example, a station is in sub-net 1, in 'Degraded mode'
and has an alarm, all the horns in sub-net 2 are also switched on. The horns
that are switched on in sub-net 2 can however no longer be deactivated by the
station in 'Degraded mode' (in sub-net 1).
If horns are connected to the station in 'Degraded mode' in sub-net 1, they can
only be deactivated by a station in sub-net 1.
See also
2 Guidelines for SAFEDLINK networking [ 129]
8.16.2 Guidelines for SAFEDLINK networking
Observe the following guidelines for the SAFEDLINK networking:
Lines for the system bus and for the DC power supply must be arranged
separately.
Networking via Ethernet is not in compliance with EN 54.
When using a repeater (SAFEDLINK) and interface module (DL485/13-xx-ST-
SBT), the earth fault monitoring of the network cabling is limited.
The number of BACnet clients for management stations is limited to 2 per
SAFEDLINK network.
The following table shows the most important parameters of the networking types.
Parameters FCnet/SAFEDLINK FCnet/Ethernet (sub-net)
Max. length of line between the stations
1
1000 m 100 m
(without switch or router)
Max. number of stations 32 14 (incl. router station)
Max. number of stations that can be networked via
FCnet/SAFEDLINK, without BACnet configuration
(e.g., management station)
32
Max. number of stations that can be networked via
FCnet/SAFEDLINK, with BACnet configuration
(e.g., management station)
16
Max. distance length between the repeater and the
stations
1000 m in each case

Table of Contents

Other manuals for Siemens FS20

Related product manuals