Planning the networking of the stations
8
132 | 242
8.16.5 Specifications for electric Ethernet
Please observe the following points:
● CAT5/CAT6 Fast Ethernet cables must be used for networking via Ethernet.
● A crossed cable must be used for the link between two ↑ stations via the
Ethernet.
● When networking via electric Ethernet only (not EN 54-compliant), a maximum
number of 32 stations an be connected to each other by means of a hub or
switch (do not use crossed cables).
● When networking via FCnet/Ethernet (not EN 54-compliant), a maximum
number of 14 stations (incl. router station) can be connected by means of a hub
or switch (do not use crossed cables).
● With cable lengths longer than 100 m, a switch or router must be used for the
amplification of the signals (do not use crossed cables).
8.16.6 Guidelines for BACnet connections
↑ BACnet connections for ↑ management stations are subject to the following
guidelines:
Parameters System limits
Maximum number of management stations (↑ BACnet
clients with access to each ↑ station)
2
Maximum number of BACnet clients total * 64
Maximum number of FS20 stations per ↑ SAFEDLINK
network (sub-net) with management stations
16
Maximum number of FS20 stations per FCnet/LAN
(extended network) with management stations
64
Table 34: System limits for BACnet connections
* Each additional BACnet client (e.g., STT20, Desigo PX controller) may only
access one station.
You will find other potential restrictions for MM8000 or GMA
relevant description and Release Notes.
Limitations
Fire control panels with PMI & mainboard FCM2004 cannot be connected to a
management station.
Compatible management stations
You will find information about the compatibility of management stations in the
corresponding documentation for the management system.